CR5395 Series Datasheet by CR Magnetics Inc.

Q AWARNING MAGNH‘S Cancer www.msmmngmgw
64
Relays, Switches, & Sensors
D
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M
NTI
Direct Current Sensing Relay
CR5395 Series
VOLTAGE LOAD TYPE
240 VAC
240 VAC
N.O. CONTACT N.C. CONTACT
Resistive
Motor
20A
2HP
10A
1/2 HP
125 VAC
28 VDC
Motor
Resistive
1HP
20A
1/4 HP
10A
The CR5395 Series, Direct Current Sensing Relay provides a
precision and cost effective method for monitoring Direct Cur-
rent. Magnetic Modulator Technology is utilized for the current
sensing to provide a stable and highly repeatable current trip.
The current-carrying wire is routed through the opening extend-
ing through the top of the case. When current reaches the level
set by the trip point adjustment, the relay trips and starts the ad-
justable timer. After the timer cycles the electromechanical relay
energizes.
Applications
DC motor drives
Battery Chargers
Power Supply Management
Uninterruptible Power Systems
Motor Application
Features
Variable Trip Point and Time Delay
Bi-polar
Monitors Currents from 1.0 ADC to 100 ADC
Electrical Isolation Between Circuits
Output Relay Rated up to 20 Amps
LED Trip Status Indicator
Dead Band Prevents Relay Chatter
Calibrated Dial
External Current Transformers Available
Specifications
Mounting:
3/16” dia. clearance holes on 115/16”by 215/16”centers
Environmental:
Operating Temperature: -30° C to +70° C
Storage Temperature: -55° C to +85°
0-95% RH, Non-condensing
Input Supply Power:
Typical 80mA Max 100mA
Sensed Current: Max. Continuous: 200% Full Scale
Altitude: 2000 meters max.
(Contact factory for High Altitude applications)
Weight 0.5 LBS.
Regulatory Agencies
OUTPUT OPTIONS
The Relay is available with three different output
configurations, electromechanical relay, op-
toisolated NPN transistor or ZeroCrossing op-
toisolated triac. Specify desired selection in part
number.
DC SWITCHING (-NPN)
Vce (full off): 30 VDC max.
Isink (full on): 120 mADC max.@ rated full-on
Vce (full on): 1.5 VDC @ 120 mADC Isink
Off state leakage current: 5ua @ 30 VDC
(typical)
Terminals: 21/4” Male QC
RELAY (-ELR)
Arrangement: 1 Form C (SPDT)
Contact Material: Silver-cadmium oxide
Terminals: 31/4” Male QC
Mechanical Life: 10 million operations,
typ.@ rated load
Electrical Life: 100,000 operations,
typ. @ rated load
Initial Contact Resistance:
50 milliohms max. @ 500 mA, 12 VDC
Contact Rating: UL508/873 & CSA
AC SWITCHING (-TRC)
Off state voltage: 240 VAC RMS max.
Minimum switch voltage: 24 VAC RMS
On state current: 500 mA RMS max. continuous
Switching mode: Zero Crossing
Off state leakage: 60 ua @ 240 VAC max.
Terminals: 2 @ 1/4” Male QC
E234389
N‘uwml 1F ma [2) w», u u, ”2 Null ouvwv zmmmmm m Mus m m was “WW 0 BE "-EIIIIIO' "5a a? . ,. u . 75 m “H "mm" flou‘mw‘c (wtm IZIHDLB EM _ Macy” _ [v 7] [71¢] 13 El low: mew w m, °'"9K,,\ ! 8 [2:5] momma - . w N ‘ ° ‘7’ '1’ 3% gnrrsu :53: ‘ 1 WI 4‘ ma m - a ‘32:! 2" 03! “’0‘ 264' WE ancs culnsu! mmmwau comcnow W Wes
65
Direct Current Sensing Relay
CR5395 Series
OUTLINE DRAWING
A
B
C
D
Remote Current Transformers CRDCS - Series
Relays, Switches, & Sensors
D
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M
NTI
SUPPLY VOLTAGE
ACV - 85 to 265 VAC/VDC
24D - 24 VDC
All supply voltage tolerances
are ± 10 %
Top view of Current Sensing Relay Shown with Remote Current
Transformer Option (-R)
PART NUMBER
CR5395 - - - - - - -
CRDCS
A B C D
-100
2.88
73.16
1.60
40.58
12
304.8
0.79
20.07
-200
3.25
82.55
1.75
44.45
12
304.8
0.82
20.83
TRIP STATUS
EH - Energized on High, trips
when sense current is above trip
point and returns to non-trip
status when sense current is
below the trip point.
EL - Energized on Low, trips
when sense current is below trip
point and returns to non-trip
status when sense current is
above the trip point.
LH - Latch on High, trips when
sense current is above trip point
and remains tripped until
supply power is removed.
LL - Latch on Low, trips when
sense current is below trip point
and remains tripped until supply
power is removed.
TRIP RANGE
110 - 1.0 to 10 ADC
330 - 3.0 to 30 ADC
660 - 6.0 to 60 ADC
101 - 10 to 100 ADC
The trip ranges shown are for
one wire pass through the
window opening. The trip range
may be proportionally lowered
with additional wire passes
through the window.
TRIP POINT DIAL
CD - Calibrated Dial
FP - Fixed Trip Point
(Specify value of fixed
trippoint with order)
3
5
10
15
30
20
CURRENT TRIP
D
25
No adjustment
dial provided with
the fixed set
point option
- CD - FP
-3.30 trip range shown
OUTPUT OPTIONS
ELR
Electromechanical
Relay
NPN
Optoisolated
NPN Transistor
TRC
Optoisolated
Triac, Zero Crossing
NC NO COM
-
+
+
TRIP ON DELAY
A - .5 to 6 Sec.
B- 2 to 25 Sec.
C- .1 to 1 Sec.
X- none
Time-on delay is the time from when the relay trips to
when the output energizes. The ranges are
guaranteed minimum, actual range may be slightly
greater.
I- INTERNAL TRANSFORMER
R1 - REMOTE TRANSFORMER
w/ CRDCS-100
(1.60” window diameter)
R2 - REMOTE TRANSFORMER
w/ CRDCS-200
(1.75” window diameter)
Example Part Numbers:
CR5395-EH-ACV-110-CD-ELR-I (Relay with CT on board)
CR5395-EL-24D-330-CD-NPN-R1 (Relay with external CRDCS-100)